1 fileBefore designing an electrical control panel, you need to understand motor power, current, protection devices and cable selection. These are the basic requirements for preparing an electrical drawing and selecting the correct components. This lesson explains these concepts with practical examples, including a 15 kW motor calculation.
This is Video 2 of the FixIt Daily Industrial Control Panel Designing & Wiring: Basic to Advance series. If you are new to this series, start with our previous lesson: Electrical Automation Basics in Hindi – Beginner to Advanced.
What You Will Learn
In this lesson, you will understand five important areas of electrical control panel design:
- Component codes and electrical symbols used in control panel drawings.
- kW and HP conversion for different motor power ratings.
- Motor current calculation for DC, single-phase and three-phase systems.
- Wire size selection using current calculation and cable capacity tables.
- How to read a practical motor power circuit drawing.
What You Need
You do not need a complete control panel or automation equipment for this lesson. You can understand the concepts using the video and its drawing.
Required learning materials:
- A notebook and pen for writing important formulas.
- A calculator for motor power and current calculations.
- Basic knowledge of electrical components.
- The free electrical drawing in Downloads for this video above.
- A computer or mobile phone to follow the electrical drawing.
You can also explore the FixIt Daily Drawings & Documents Library to find other electrical drawings, documents and learning resources.
Keep the drawing open while watching the video. It will help you identify the components and understand the power circuit.
How It Works
Electrical control panel design starts with identifying the load. The load may be a motor, heater or lamp. You need to know its power, supply voltage and current before selecting the protection devices and cables.
The motor current is especially important because the selection of breakers, contactors, overload protection and wires depends on it.
An electrical drawing also uses identification codes for every component. These codes help electricians understand the circuit and match the drawing with the actual components inside the control panel.
Step 1: Understand Component Codes and Electrical Symbols
Every electrical component in a control panel drawing has a short identification code. Usually, letters represent the component type, while numbers identify individual components.
For example:
| Component Code | Component Name |
|---|---|
| MCCB | Main Circuit Breaker |
| CB1, CB2 | Circuit Breaker |
| Q1, Q2 | Motor Circuit Breaker |
| F1, F2, F3 | Fuse |
| KM1, KM2 | Magnetic Contactor |
| R1, R2 | Relay |
| T1 | Timer |
| SW1, SW2 | Selector Switch |
| PB1, PB2 | Push Button |
| M1, M2 | Motor |
Understanding Basic Electrical Symbols
- NO (Normally Open): The contact remains open at rest and closes when operated.
- NC (Normally Closed): The contact remains closed at rest and opens when operated.
- Push Button NO: Used for a start command in the example.
- Push Button NC: Used for a stop command in the example.
- Selector Switch: Selects Manual, Off or Auto mode.
- Contactor Coil: Operates the contactor when the coil is energised.
- Relay Coil: Operates a relay for control switching.
The same component code is used in the electrical drawing and on the actual component inside the panel. This makes wiring, testing and troubleshooting easier.
Always follow the component legend of your own project because identification codes may differ between drawings.
Step 2: Understand kW and HP Conversion
Motor power is generally expressed in kilowatts (kW) or horsepower (HP). Some motor nameplates show power in kW, while others use HP.
Before calculating motor current, you may need to convert HP into kW.
Conversion Formulas
| Conversion | Formula |
|---|---|
| HP to kW | kW = HP × 0.746 |
| kW to HP | HP = kW ÷ 0.746 |
Practical Example
If a motor has a power rating of 10 HP:
10 × 0.746 = 7.46 kW
Therefore, 10 HP is approximately 7.5 kW.
Common Motor Power Conversion Table
| Motor Power (HP) | Motor Power (kW) |
|---|---|
| 1 HP | 0.75 kW |
| 2 HP | 1.5 kW |
| 5 HP | 3.7 kW |
| 7.5 HP | 5.5 kW |
| 10 HP | 7.5 kW |
| 15 HP | 11 kW |
| 20 HP | 15 kW |
These are rounded values for learning and quick reference.
Step 3: Calculate Motor Current
Motor current calculation is one of the most important parts of electrical control panel design.
You must calculate or identify the current before selecting the protection devices and cables.
Current Calculation Formulas
| Electrical System | Current Formula |
|---|---|
| DC, Heater and Coil | I = P ÷ V |
| Single-Phase AC | I = P ÷ (V × PF) |
| Three-Phase Motor | I = P ÷ (1.732 × V × PF × η) |
Meaning of the Formula Symbols
| Symbol | Meaning |
|---|---|
| I | Current in Amperes (A) |
| P | Power in Watts (W) |
| V | Supply Voltage |
| PF | Power Factor |
| η | Motor Efficiency |
| 1.732 | Square root of 3, used for three-phase calculations |
Practical Example: 15 kW Three-Phase Motor
Let’s calculate the approximate current of a 15 kW motor using the values shown in the video.
Given Information
| Parameter | Value |
|---|---|
| Motor Power | 15 kW |
| Supply Voltage | 380 V |
| Phase | 3 Phase |
| Power Factor | 0.85 |
| Efficiency | 0.90 |
Step 1: Convert kW into Watts
15 × 1000 = 15,000 W
Step 2: Calculate the Denominator
1.732 × 380 × 0.85 × 0.90 = 503.5
Step 3: Calculate the Current
I = 15,000 ÷ 503.5
I = 29.8 A
Calculated Result: Approximately 30 A
This calculation is an educational example. The actual motor nameplate current is the final reference for real component selection. Use the calculation as a check, not as a replacement for the nameplate.
Step 4: Select the Correct Wire Size
After calculating the motor current, the next step is selecting the appropriate cable size.
A cable must have sufficient current-carrying capacity for the application. The video explains a simple three-step method.
Three Steps for Wire Size Selection
- Find the motor current from the nameplate or calculation.
- Add a 25% margin by multiplying the current by 1.25.
- Select the first suitable wire size from the current capacity table.
Practical Wire Size Calculation
For the 15 kW motor example:
| Calculation | Result |
|---|---|
| Motor Current | 30 A |
| Additional Margin | 25% |
| Calculation | 30 × 1.25 |
| Required Current Capacity | 37.5 A |
Now compare the result with the cable table.
Wire Size and Current Capacity Table
| Wire Size | Approximate Safe Current |
|---|---|
| 1.5 mm² | 13 A |
| 2.5 mm² | 18 A |
| 4 mm² | 24 A |
| 6 mm² | 31 A |
| 10 mm² | 42 A |
| 16 mm² | 56 A |
For a required current capacity of 37.5 A:
- 2.5 mm² = 18 A — Not suitable.
- 6 mm² = 31 A — Not suitable.
- 10 mm² = 42 A — Meets the example’s calculated requirement.
Selected Wire Size: 10 mm²
These are approximate values for copper PVC wire in conduit, as shown in the lesson. Always check the cable manufacturer’s current rating table before selecting a cable for an actual installation.
Also remember that very long cables can experience voltage drop. This needs a separate check during practical cable selection.
Step 5: Read a Real Electrical Power Circuit Drawing
After understanding component codes, motor current and wire size, you need to apply this knowledge to an actual electrical drawing.
The video shows a practical power circuit for a lift station pump.
Main Components Used in the Drawing
| Component | Details | Function |
|---|---|---|
| Q3 | GV2ME20, setting range 13–18 A | Motor circuit breaker |
| KM3 | LC1D18M7, 18 A | Magnetic contactor |
| Terminal Blocks | 13, 14, 15 and E | Motor cable connection |
| Motor Cable | 6 mm², 4 cores | Three phases and earth |
| M2 | Lift Station Pump 1 | Motor load |
Motor Details in the Drawing
| Parameter | Value |
|---|---|
| Voltage | 380 V |
| Supply | Three-Phase |
| Rated Current | 15 A |
| Starting Method | DOL (Direct On Line) |
Understanding the Power Flow
The power circuit follows this connection sequence:
Supply → Q3 → KM3 → Terminal Blocks → Motor
Here’s what happens:
- The incoming supply reaches the motor circuit breaker.
- The supply passes through the contactor.
- The connection continues through the terminal blocks.
- The motor receives the three-phase supply through the motor cable.
This example helps you understand how electrical components are arranged in a power circuit drawing.
Important: The 15 kW motor current calculation and the lift station pump drawing are separate examples in the video. The pump drawing specifies a rated current of 15 A. Do not confuse these two examples.
Testing Before You Switch On
Before energising an electrical panel or motor circuit, check the following points:
- Confirm that component codes match the electrical drawing.
- Check breaker and contactor details against the project requirements.
- Verify the selected cable size and current-carrying capacity.
- Check power connections against the drawing.
- Verify motor terminal connections and earthing.
- Confirm that the circuit has been inspected and tested by a qualified person before energising.
Common Mistakes
- Selecting components without calculating current — Always identify the load current before choosing protection devices and cables.
- Confusing kW and HP — Understand both units and use the correct conversion formula before calculating current.
- Selecting wire size only by motor power — Calculate current and check the manufacturer’s cable capacity table.
- Ignoring component codes — Follow the drawing legend to identify the correct components in the panel.
- Ignoring motor nameplate information — Use the actual nameplate current for final component selection.
Safety
Electrical panel work can be dangerous. Always isolate the supply, lock it off and test for dead using a proper voltage tester before working on the circuit. Follow local electrical safety rules, and ensure practical electrical work is performed by qualified persons only.
FAQ
What should I know before designing an electrical control panel?
You should understand the load, supply voltage, motor power and current. These details help you select suitable protection devices, contactors and cables.
How do I calculate the current of a three-phase motor?
Use the formula I = P ÷ (1.732 × V × PF × η). You need motor power, supply voltage, power factor and efficiency for this calculation. Always use the actual motor nameplate current for final selection.
Why do we add a 25% margin when selecting wire size?
The video uses a 25% margin to provide additional room for factors such as heat, ageing and starting current. Final cable selection must also consider the installation conditions and manufacturer’s current rating data.
What is the difference between kW and HP?
Both kW and HP are units used to express motor power. You can convert HP into kW by multiplying by 0.746, or convert kW into HP by dividing by 0.746.
Why are component codes important in electrical drawings?
Component codes help identify each device in the drawing and match it with the actual component inside the control panel. They make wiring, testing and troubleshooting easier.
Continue Learning with FixIt Daily
Electrical control panel design is a step-by-step learning process. Continue with the next lessons in the FixIt Daily series to understand AC and DC, motor control, PLC, VFD, HMI, SCADA and industrial automation.
Explore more learning resources:
- Explore FixIt Daily Courses – Visit the courses section for electrical training resources and course updates.
- Browse Electrical Drawings & Documents – Find electrical drawings, documents and practical learning materials.
- FixIt Daily Services – Explore drawing, panel consultation and team training services.
- Official FixIt Daily Profile & Links – Find the main FixIt Daily resources and official links.